TCV94 Terminator Profile Low Flow Commissioning Valve PN25 15mm

Pressure/Temperature Rating

  • PN 20 Series B
  • 20 Bar from -10° TO 120°C

Test Pressure Hydraulic

  • Shell 30 Bar

Specification

  • Threads to BS 21 taper (ISO 7)
  • Intergral ball valve with Venturi orifice
  • Measuring device
  • Upstream connection union nut adapter

Suitable for measurement of flow between 0.007 l/s @ 0.5kPa signal and 0.316 l/s @ 4.6 kPa signal using a low lost manometer

Download the Data Sheet



Component Material Specification
Valve body and stem Brass CZ 122
Insert EPDM Special  
Cap Brass CZ 122
Dimensions
Part No Size C D E/F Kg
TCV9404 15 105 75 52 0.6
TCV9406 20 106 75 52 0.55
Signal Coefficients kvs
Size 15 20
Venturi 3 4 6 9 12
kvs 0.36 0.6 1.38 3.04 5.3

Specification Text

Where low flow commissioning stations are marked DN15 a Low Profile Terminator Commissioning Valve should be installed. To include double regulating profiled ball valve with memory stop, flow measurement is by means of interchangeable venturi. Each line size should have at least two diameters of venturi available to accommodate various flow rates.