TCV90 Terminator Commissioning Valve

Pressure/Temperature Rating

  • PN 25
  • 25 Bar from -10° to 120°C screwed male /female
  • Optional Connection - check pipe material

Specification

  • Threads taper
  • Integral ball valve
  • Venturi orifice measuring device
  • Upstream connection union nut adapter with interchangeable ends to suit different types of pipe
  • Fitted with two double action TP02N pressure test valves

Download the Data Sheet


Material Specification

Component Material Specification
Venturi Orifice brass CZ121 BS 2874
Union Nut brass CZ122 BS 2874
Ball Valve brass CZ122 BS 2874
Tail Piece brass CZ122 BS 2874
Pressure Test Valve brass CZ122 BS 2874
Dimensions
Part No Size C D E/F Kg
TCV9404 15 105 75 52 0.6
TCV9406 20 106 75 52 0.55
TCV9008 25 125 95 55 0.95
TCV9010 32 145 120 59 1.4
TCV9012 40 164 120 60 2.0
TCV9016 50 191 150 66 3.0
Signal Coefficients kvs
Size 15 20 25 32 40 50
Venturi 3 4 6 9 12 10 14.5 13 19 15 22 18 31.55
kvs 0.36 0.6 1.38 3.04 5.3 3.69 7.88 6.6 14.3 8.6 20 12 42

Suitable for measurement of flow between 0.007 l/s @ 0.5kPa signal and 0.316 l/s @ 4.6 kPa signal using a low lost manometer

Specification Text

Where commissioning stations are marked DN15 - DN50 a Terminator Commissioning Valve should be installed. To include double regulating ball valve with memory stop, flow measurment is by means of interchangable venturi. Each line size should have at least two diameters of venturi availible to accommodate various flow rates.